Voltage Drop Calculator
Calculate voltage drop for copper or aluminum wire on DC, single-phase or three-phase circuits. See the drop in volts and percent, the voltage at the load, and the smallest wire size that keeps the drop within 3% or 5%.
- NEC Table 8 resistance
- 14 AWG to 500 kcmil
- 3% and 5% sizing
Voltage Drop Calculator
Voltage drop, percent drop and the smallest wire that stays within 3%.
Voltage drop
All wire sizes for this circuit
| Size | Drop | Percent |
|---|
Your numbers stay in your browser. Nothing is sent or saved.
Voltage Drop Formula
The 2 counts the current going out and back on two wires; three-phase circuits use √3 instead. Divide by the number of conductors when you run parallel sets.
How to Calculate Voltage Drop: Example
What Voltage Drop Is Acceptable?
The National Electrical Code recommends, in informational notes, no more than 3% drop on a branch circuit or a feeder and no more than 5% in total from the service to the farthest outlet. These notes are advice for efficient operation rather than enforceable rules, but many designers and some local codes treat them as a requirement. Motors, LED drivers and electronics run hotter or misbehave when the voltage at the load is low.
Maximum Distance for 3% Drop at 120 V
One-way length for single-phase 120 V copper circuits:
| Copper size | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 14 AWG | 59 ft | 39 ft | 29 ft | 20 ft |
| 12 AWG | 93 ft | 62 ft | 47 ft | 31 ft |
| 10 AWG | 149 ft | 99 ft | 74 ft | 50 ft |
| 8 AWG | 231 ft | 154 ft | 116 ft | 77 ft |
| 6 AWG | 367 ft | 244 ft | 183 ft | 122 ft |
| 4 AWG | 584 ft | 390 ft | 292 ft | 195 ft |
| 3 AWG | 735 ft | 490 ft | 367 ft | 245 ft |
Double the distances for 240 V circuits. Voltage drop only tells you about losses; the wire must still meet the ampacity rules in NEC Table 310.16 and the breaker size for the circuit.
Wire Resistance by Size (NEC Chapter 9, Table 8)
| Size | Copper (Ω/1,000 ft) | Aluminum (Ω/1,000 ft) |
|---|---|---|
| 14 AWG | 3.07 | 5.06 |
| 12 AWG | 1.93 | 3.18 |
| 10 AWG | 1.21 | 2.0 |
| 8 AWG | 0.778 | 1.28 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 3 AWG | 0.245 | 0.403 |
| 2 AWG | 0.194 | 0.319 |
| 1 AWG | 0.154 | 0.253 |
| 1/0 AWG | 0.122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.159 |
| 3/0 AWG | 0.0766 | 0.126 |
| 4/0 AWG | 0.0608 | 0.1 |
| 250 kcmil | 0.0515 | 0.0847 |
| 300 kcmil | 0.0429 | 0.0707 |
| 350 kcmil | 0.0367 | 0.0605 |
| 500 kcmil | 0.0258 | 0.0424 |
Values are DC resistance at 75°C, solid wire for 14–10 AWG and stranded for 8 AWG and larger. For large conductors on AC with a low power factor, the NEC’s Table 9 impedance gives a slightly more precise result.
How to Reduce Voltage Drop
- Use a larger wire size (a smaller AWG number). Each step of about three sizes halves the resistance.
- Shorten the run, or move the panel or a subpanel closer to the load.
- Run at a higher voltage: the same power at 240 V draws half the current of 120 V.
- Use copper instead of aluminum, or run parallel conductors on large feeders.
Frequently Asked Questions
How do I calculate voltage drop?
For single phase or DC, multiply 2 × current × resistance per foot × one-way length. For three phase, use 1.732 instead of 2. Divide by the source voltage for the percentage.
What is the maximum voltage drop allowed by the NEC?
The NEC recommends 3% for a branch circuit or feeder and 5% total in its informational notes. They are recommendations, not mandatory rules, unless your local code adopts them.
What size wire do I need for 100 feet at 20 amps?
On 120 V copper, 10 AWG gives about 4.03% and 8 AWG about 2.59%, so 8 AWG keeps the drop under 3%. On 240 V, 10 AWG gives about 2.02%.
Does voltage drop depend on the load?
Yes. Voltage drop is proportional to current, so the same wire drops twice as many volts at twice the amps.
Is the length one way or round trip?
Enter the one-way distance from the source to the load. The formula already doubles it for the return path.
How much voltage drop on 12 gauge wire?
About 0.386 V per amp per 100 ft one way on copper (2 × 1.93 ÷ 10). At 15 A over 100 ft that is 5.79 V, or 4.83% at 120 V.
Related Calculators
Sources
- National Fire Protection Association. NFPA 70, National Electrical Code, Chapter 9, Table 8: Conductor Properties (DC resistance at 75°C, ohms per 1,000 ft).
- NFPA 70, National Electrical Code, 210.19(A) Informational Note No. 4 and 215.2(A) Informational Note No. 2 (3% voltage drop for branch circuits or feeders, 5% total, recommended for reasonable efficiency).
For estimating only. Electrical work must follow the NEC as adopted locally and the conductor ampacity, temperature and termination rules; have a licensed electrician design and install circuits.